Thank you for helping me to clarify this in my mind.
So given my need for a total of 40 modules of 208 load, I think I'm best off coming from the main distribution with 3 2-wire (+ground) 208v circuits, each driving a third of the modules, and not a single 3-phase circuit that would have to be...
I have a situation where a building only has a 208/120 feed.
I need to power a rack of ac to dc rectifier modules that each require >200vac to work.
The outputs of these rectifiers are all tied together and share the dc load, so the load balance should be pretty close.
If I balance the...