Finally received the data from the fire flow.
static 81 psi
1" 80 psi 112 gpm
1.25" 79 psi 223 gpm
1.5" 77 psi 322 gpm
2" 69.5 psi 664 gpm
2.5" 57.5 psi 1115 gpm
4.5" 18 psi 1680 gpm
Fire hydrant will be on 6" pvc line at 300' from 8" tie in then branch 2" each...
Just came across this forum, hope to be able to interact and contribute in the future. For now I have a basic question. I am working on a plan to extend 400 lf of 6" pvc line into a subdivision. The line will then tee with 2" lines perpendicular to the 6" going 400 lf in each direction...