    MODELING A SINGLE-LINE TO GROUND FAULT

    You don't have fault current because the system is ungrounded. Put a ground reference in your model whit moderate impedance to see some fault currents and voltages. For example try including a reactor in your model whit very hig impedance. Excuse my bad english.