Thanks guys, I went and checked the coils with the bars off for continuity with the meter and you are right. The coil pairs are
U1&U2
U3&U4
V1&V2
V3&V4
W1&W2
W3&W4
So I will bind U1 to W4, V1 to U4 and W1 to V4
I really appreciate the quick and accurate feedback and reference documents
Most 3 phase motors I work with are 6 lead, but I have this 12 I'd like confirmation on the wiring.
I think I already know the answer to this, but I'd just like a sanity check.
I'm trying to wire this motor for 220.
Image
https://ibb.co/4ps2GZV
I have the jumper plates configured property for...