@gtaw
Sry i couldn't finde your email add.
This is the photo of inside the tankhttps://files.engineering.com/getfile.aspx?folder=385584df-437a-48dd-a4f0-6b74d19aaca0&file=Screenshot_20200822-004103.jpg
@gtaw
Those pics were amazing.
It seem we have a same problem. I'll send more photo from inside of the tank. Before and after cleaning.
There are many mounds of brown jello.
Now i have little problem with sending photo. I'll be send them as soon as i can.
Best regards.
@littlench
I said that. Temp. Is ambient. Between 30-50°C.
Based on API 571 clause 4.5.1 all of the s. S. 300 series has been affected from from Cl scc.
Now i dont have the doc. But tommorow i can say to you the thickness.
Diameter of the tank is 12m.
Water analys is attached.
COD=24 ppm
BOD=...
We make this tank. All welders were qualified. All the tank has been tested by RT.
Water came from the river, and we treated the water, some part of the water go to the DM unit and some part of the water go through the active carbon and come into this tank.
This case have been happened after...