In our country phase voltage is 230v but in worse case it may goes below 200v. Sometimes during irrigation period, water pump motor burnt out. Of course current increases with the decrease of terminal voltage. I wanted to know the rating of safest CB to avoid this case.
P=5hp=746*5w=3730w
V=230v
I=P/V=3730/(230*0.75)=21.6A [where pf=0.75]
How the full load current of this motor be 28A? Why CB would be 250% of full load current? Usually, do the CBs not allow 3 to 5 time of rated current?