Thanks to everyone that answered, very helpful!
One follow-up question, if I need to increase my hot flow by 50% (i.e. from 0.11 kg/s to 0.165 kg/s) and keeping the same hot inlet and outlet temperatures, can I simply increase my cooling flow by 50% (with the same cooling inlet and outlet...
Hi Everyone,
I currently have the following issue that I need help with:
I have a tube in tube heat exchanger.
On the inside of the tube I have a hot liquid (assume to be the same as water) flowing at 0.11 kg/s.
This enters at 90 deg.C and leaves at 60 deg.C. That is 13.9kW of cooling.
On...