Thanks for all your help Spartan. I will check out the Orenco system.
Zoeller does have it listed on their website. It is in the products tab and they have a ton of information on it. The filter has a lifetime warranty.
I'll check into the security measure as well. That is definitely a...
Here is the system I'm thinking about. It looks like it would be ideal. Its in dwg format.http://files.engineering.com/getfile.aspx?folder=01086926-7519-410e-85a1-491041bd8493&file=sk1965.dwg
Thanks Spartan. We are taking all the items you mentioned into consideration. It is a very unique situation I'm dealing with.
I found an ideal STEP system by Zoeller. Does anyone have experience with Zoeller products? Are they on par with Fylgt(sp?) or Myers Pumps? Looks like they have...
Ussuri,
Are you saying I should not use a grinder pump but use a STEP type system instead? My only concern about using a non-clog pump is the forcemain will have to be larger than the forcemain for a grinder pump.
I'm only going to be pushing 20 gpm @ 20 ft. TDH. I'm thinking my GPM won't be...
Thanks Spartan. Let me expand a little bit. The existing septic consists of 2 nitrification fields and tanks. The first one was construction in 1966 and the 2nd in 1984. The overall site handles approximately 12,500 GPD of waste from a elementary school. Due to our constraints we have to...
Here's the deal. I'm the civil site engineer on a school addition with an existing septic system we want to use.
The architect wishes to lower the floor elevation of the new addition and that means the sanitary invert will be lower than the existing septic tank I need to tie into. I can't...