Use breaker & relaying only, IF you have compliant secondary overcurrent protection with T450.3(A) note 2.
Note this transformer, at 5MVA, is recommended by IEEE Buff Book to have 87T/86T differential protection and 63FP/63X rapid pressure rise protection, also.