Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations SSS148 on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Recent content by txlineman

  1. txlineman

    Pole transformer fusing

    7.2kv and 14.4 kv conventional single phase transformers 1/3 and 1/5th rule will get you close. For example 50 kva single phase @ 7.2kv = 16.7 amps would get a 15 amp link fuse. this applys to K type fuses. Hope this helps. JB

Part and Inventory Search