or the addition of 50% of rated load, shall not exceed
That begs some questions.
1> Is motor starting considered to be the rated current or the starting current.
2> Is the load the load in KVA, (motor starting 6 x rated KVA), or the load in kW, (motor starting 3 x rated kW)
Therefore, I interpret that this 50% loading applies only to the alternator.
Maybe not a valid interpretation:
For engines driving generators, the transient frequency variations shall meet the ABS."
Anecdote Alert;
Years ago, a country faced a power crisis with 6hr on and 6hr off power rationing.
A supplier ordered a large number of standby sets.
Whoever sized the sets failed to take into account the large amount of A/C loads.
By trial and error, at over 6 sites, I developed a good understanding of just how much a standby set could handle.
My findings, that were borne out by success sizing a lot of standby sets in the years following:
1. A standby set will only start a motor rated at 50% of the set capacity if the motor is the only load.
2. A standby set will start a motor rated at 33% of the set capacity with acceptable voltage drop for other loads.
Notes:
20% voltage drop or not? 20% drop corresponds to 80% voltage.
A common drop out point for magnetically held devices is 80%.
At 50% sizing, most magnetically held devices would drop out, implying more than 20% voltage drop.
At 33% sizing, all magnetically held devices would hold in, implying less than 20% voltage drop.
Notes on Notes:
For a prime rated set, add 10% to the set capacity before using these guidelines.
Example, a 50 KVA rated prime power set will be a re-rated 55 KVA standby set.
Consider it to be a 55 KVA set for the purpose of these sizing suggestions.
And another Note:
If you use the free generator sizing software from Caterpillar the software will recommend a larger set that suggested by these guidelines.
The software uses a default "allowable voltage drop" setting.
You may change the "allowable voltage drop" setting in the software.
After sizing the set to ABS standards, you may wish to double check it against these suggestions.
Or use the Cat sizing software, (with the default "allowable voltage drop" changed to ABS values).