  1. DM61850

    Short Circuit Calculation - Point to Point Method excel sheet

    Go read the KVA or MVA method by Moon. https://arcadvisor.com/files/ShortCircuitABC.pdf
  2. DM61850

    Relay setting for Radial 115kv tranamission line

    All the transformers I have seen that were hooked up to transmission had differential. The distance relaying I saw never saw through the transformer and we just lived with the fact that if a hard fault happened near the high side, both would trip. I don't think though that transformers when...
  3. DM61850

    Under What Circumstances a PE May Lose Their License

    In the Texas Board of Engineers newsletter, the only people that get booted are people who just got convicted of felonies.
  4. DM61850

    Under What Circumstances a PE May Lose Their License

    It is pretty hard to get your license revoked. You have to show either persistent willingness to violate the boards regulations or be negligent with fatalities. Being unethical and doing stuff like bidding on projects against your employer isn't enough. It is much easier to get sued though I...
  5. DM61850

    Interpretation of Low Magnetizing Current CTs (Current Transformer)

    You want low magnetizing current so that your measurements at low current don't have a lot of error. I suspect that they want you to get a low ratio CT, something like a 50/5 so the amount of current in your secondary circuit is large in comparison to the excitation current.
  6. DM61850

    Sympathetic Trip at Grounded Y Delta Power Transformer

    Your generator transformer is acting like a ground source. Why do you need two other ground sources?
  7. DM61850

    Professional Development

    bacon4life, This forum is extremely beneficial. I though wouldn't forget that there is a lot here that you wouldn't understand without having taken those applicable classes. We had potential interns (sophomores) try to answer a basic voltage divider with a resistor in series with two parallel...
  8. DM61850

    Sympathetic Trip at Grounded Y Delta Power Transformer

    Protolash, A simpler solution would be to just remove the ground connection on the second set of wye-ground-delta transformers. I don't understand why they were ever grounded.
  9. DM61850

    Professional Development

    Honestly the most bang per buck for me has been in this order: 1. Try to find old people to talk shop with, online or offline. If you can't find people to talk shop with, you are only going to grow with the work you are given. 2. Being part of an industrial planning or standards development...
  10. DM61850

    Breaker trip/close interposing relays

    SEL relays often have a set of contacts that are high current interrupting and you often can get by without using an interposing relay. Utilities often don't want to use an interposing relay because it is a single point of failure. Some places don't even both with using high current...
  11. DM61850

    Offered 50% share in company.

    Couldn't you just take that initial 700k offer money and hire a few hot shot engineers? The firm only has value as to what the customer perceives as adding value. Having hot shot engineers is the only thing that will add value and make it easier to get work.
  12. DM61850

    Current Harmonics based on Source Impedance

    Vter, I think you want to get a copy of the IEEE Brown Book and IEEE 519. The brown book has a section in it explaining harmonics, how to model equipment, and how to mitigate issues. IEEE 519 has all the THD requirements for defining healthy voltages and currents. When I did a study of a...
  13. DM61850

    Relay vs PLC contorl for M-T-M transfer scheme

    If you used relays for your MTM scheme, you will have all the functions you care about built into it and you can include protective functions into those relays as well. I am coming from a protecton background and not a controls background but I would use a relay for any function that involved...
  14. DM61850

    Small Grid USA

    The market can't and won't support nuclear power or even research into new reactor designs. There are so many other options now that are cheaper and don't require sunk cost for research. Even if there existed a potential nuclear power design that was economical, no one is going to fund the...
  15. DM61850

    Sync Window: Induction Motors

    The angle shift is going to relate to how much inertia the system has. I read that most fast transfer schemes don't supervise sync so maybe this is usually a moot point but in Beckwith's materials and elsewhere, it is mentioned that fast transfer might not be possible depending on the system...
  16. DM61850

    Sync Window: Induction Motors

    How do you determine the sync window for closing in on induction motors? I came across a motor standard stating that you don't want V/Hz to exceed 1.33 (IEEE C50.41-2000) but I don't really have a way of determining how the system voltage and frequency decays to know how small I need to make...
  17. DM61850

    Current Harmonics based on Source Impedance

    Each VFD has a profile based on how many pulses it has. You probably can get a pretty good idea of what harmonics the recifier produces based on how many pulses it has. I don't know if you can back up what the harmonic currents will be based on the source impedance. You can have series and...
  18. DM61850

    Ampacities for Aluminum Overhead Electrical Conductors

    At least from what I have seen, a huge chunk of the spare capacity on the transmission system is for contingency. The NERC TPL standards demand N-1-1 contingency design requirements.
  19. DM61850

    America’s Worst Nuclear Disaster Was in California. Who Knew?

    Waross, I made it when I was growing up but it was pretty expensive at least for what I was paying for iodine. I wanted to make mercury fulminate but never felt confident playing with mercury.
  20. DM61850

    Ampacities for Aluminum Overhead Electrical Conductors

    Usually it is to for a contingency case and not normal operations. I did a study for a wind farm once that wanted to not have to upgrade their tape with the expansion of their wind farm with the reasoning that the line had a lot of extra capacity due only being able to generate when it is...