  1. Thulohot

    PRVs on same discharge line (steam)

    @ The Obturator I appreciate the feedback and will reach out to Spirax. As for the existing boilers, they are outside the scope of our project and were installed at least 5-10 years ago (not by us). As they were sold as a package by the boiler manufacturer, I assume the design is sound. I will...
  2. Thulohot

    PRVs on same discharge line (steam)

    @Latexman Yes, boiler is compliant with Section 1 and pressure vessel will be compliant with section VIII. The pressure vessel will be about 30 feet from the 4 inch header and the atmosphere is around 40 feet (total pipe length) from the boiler PRV (and header). So the pressure vessel PRV...
  3. Thulohot

    PRVs on same discharge line (steam)

    Hi, I am trying to confirm whether a PRV can be discharged into an existing PRV discharge vent. We are adding a steam heat recovery vessel which has a MAWP of 150 PSIG, with a PRV set at 30 PSIG. The existing PRV serves a steam boiler with MAWP of 200 PSIG, and PRV set at 150 PSIG. We had...