Hi all,
(Problem) Density drop significantly from operating condition to ambient condition for town gas (50mol% H2, 50mol% hydrocarbons). This result in a large very large zone distance (Zone 1, 9m) if used the calculation method in IEC 60079-10-1 (using density at ambient condition).
The...
Hi all,
Should pressure relief valve be considered as primary or secondary grade of release in IEC 60079-10-1? Section B.2.3(d) and B.2.4(d) said that relief valves can be primary or secondary depending on whether they are expected to lift during normal operation or not. My understanding is...
Hi,
I am looking for the average valve shaft diameters for different valve sizes. For example, for a 6-in valve, what is the typical shaft diameter. Are there any reference documents for it?
Thanks!