  1. ED-GEE

    Short Circuit Calculation - Point to Point Method excel sheet

    I don't have great excel skills yes a bussman pt to pt would suffice for light commercial residential applications something like 15 nodes / points …..
  2. ED-GEE

    Short Circuit Calculation - Point to Point Method excel sheet

    Happy Friday Engineers, would anyone be able to share a Short Circuit Calculation - Point to Point Method excel spread sheet? or know of a software that does this via pt. to pt. method?
  3. ED-GEE

    UNDERSIZED OCPD FOR A SWITCHBOARD

    I have a situation where there is an existing 800a fused switch feeding a new 1200a switchboard with 3 sets of 4#600kcmil + grd. I cant seem to find the code violation for that, any thoughts?
  4. ED-GEE

    3 PHASE DISTRIBUTION FEED WITH A REDUCED NEUTRAL

    Can anyone clarify and show example of a 3 phase 400A feeder with a reduced size neutral? is that even allowed by NEC?
  5. ED-GEE

    MIXING DIFFERENT SERVICES IN A PULLBOX

    All, I have a situation and I need to know NEC cite sections of the code. if I have 5 different electrical services can I commingle downstream in a crown box cables/feeders from the different services? see picture attached herewith please help
  6. ED-GEE

    manhole grounding-bonding nyc

    All, I don't see anything in the NEC code book regarding grounding bonding of manholes, any insight on how to approach this?
  7. ED-GEE

    ONE (1) OCPD FOR TWO (2) AC CONDENSER UNITS

    Wow you guys are the best so much help thank you very much!! yeah upstream one MCB main circuit breaker 60Amps controls (2) 40A unfused disconnects of which each feeds the AHU, I figured the 60AMCB is too small and said to upsize to 80Amps lets see what they say. Code to reference would be NEC.
  8. ED-GEE

    ONE (1) OCPD FOR TWO (2) AC CONDENSER UNITS

    I HAVE TWO 480V CONDENSERS FED OFF ONE 60A MCB IS THIS CODE COMPLIANT? (THEY BOTH HAVE DISCONNECTS IN LINE OF SITE) 12 Ton Unit MOP – 40A MCA – 26.4A 14 Ton Unit MOP – 40A MCA – 31.3A
  9. ED-GEE

    SECONDARY SIDE OF TRANSFORMER OCPD FOR AN AUTOMATIC TRANSFER SWITCH LOCATION

    No this is not a service the normal service room is adjacent to these two electrical rooms. The emergency power source and feeds are from 2 buildings away in the generator room service switchgear room. These 2 rooms are NEW for ATS equipment and misc panels from normal and emergency equipment...
  10. ED-GEE

    SECONDARY SIDE OF TRANSFORMER OCPD FOR AN AUTOMATIC TRANSFER SWITCH LOCATION

    this is an old building and they are trying to update the building with emergency power, I put all the ATS's in one room along with the emergency panels, I left all the transformers in a separate room along with all fused disconnects and normal panels. The transformers some are for emergency...
  11. ED-GEE

    SECONDARY SIDE OF TRANSFORMER OCPD FOR AN AUTOMATIC TRANSFER SWITCH LOCATION

    Scenario: 2 rooms one room housing ATS sw's other room housing Transformers and secondary fused disconnects for the ATS conductor protection. Can these Fused discos be in a separate room per NEC?