  1. isidore72

    Hot Oil Drain Tank with N2 Blanketing System PSV Sizing

    Dear met11, Thanks for your interest. I apologies for the confusion over the SetP, I was sizing for a multiple tanks here, just let's say Let's just assume 9.5 barG is the one for further discussion. With respect to your suggestion that unwetted case is not a valid scenario, my calculation...
  2. isidore72

    Hot Oil Drain Tank with N2 Blanketing System PSV Sizing

    Dear All, I have re-attached the attachment via Link here. To be more spcefic, the Hot oil used is Dowtherm Q Heat transfer Oil. For Wetted Vessel Case (i.e. Hot Oil vaporization case) I performed flash using Hysys to get the boiling point of Hot Oil 419 C at the relieving pressure i.e...
  3. isidore72

    Hot Oil Drain Tank with N2 Blanketing System PSV Sizing

    Dear All, I am looking for pointers to design for PSV for Hot Oil Drain Tank with N2 Blanketing System. I am designing the PSV based on Fire case and Wetted vessel scenario, and I have made the following basis and would like to know if they are correct. During External Fire Scenario, hot oil...