  1. DonQ

    MCC Starter Replacement

    Thanks for your help!
  2. DonQ

    MCC Starter Replacement

    If the AHJ has an issue with me modifying the listed assembly what would be a good option? The customer wants a soft-starter on the existing pump.
  3. DonQ

    MCC Starter Replacement

    I understand what you are saying, what if it is a thermal magnetic type? Trying to cover all bases since I am bidding a project this week with this combination.
  4. DonQ

    MCC Starter Replacement

    Does anyone know if an existing across-the-line motor starter inside a motor control center bucket can be changed to a 'soft-starter' without having any issues with NEC? Only wanting to change the starter, not the breaker, control transformer, etc. thanks
  5. DonQ

    Bad Power Factor

    Yes, they are charging...thanks
  6. DonQ

    Bad Power Factor

    When the electric service was replaced, a backup generator and automatic transfer switch were also installed for the pump station. It looks like the generator would be constantly running if the incoming power was excessively unbalanced. But I didn't setup the transfer switch either.
  7. DonQ

    Bad Power Factor

    I'm still trying to find out if the utility changed-out the metering, I really believe they have something wrong on their side!
  8. DonQ

    Bad Power Factor

    The power factor correction capacitors were removed when the VFD's were installed. Thanks..
  9. DonQ

    Bad Power Factor

    Each pump will run approx. 3 to 4 hrs a day. The pumps are set-up to only run at 55 Hz to keep the filter tanks from over-flowing. Thanks.
  10. DonQ

    Bad Power Factor

    When the drives were installed, at the same time the electric utility upgraded the service from a 480v corner grounded delta to a 277/480v wye. Line and load reactors were installed with the drive also. Thanks for all the help!
  11. DonQ

    Bad Power Factor

    Very good point, I'll check the 'power factor' information on the drive(s), I'm sure its there somewhere!
  12. DonQ

    Bad Power Factor

    What kind of issues 'could' we have with the VFD's? (Adding the capacitors)
  13. DonQ

    Bad Power Factor

    This installation has been in service for a year now, and every month the 'electric bill' indicates a 10% loss, now it has leveled out to around 20%. This is a rural electric utility.
  14. DonQ

    Bad Power Factor

    Hello, Recently a pumping station was upgraded and the 'part-wind' starters and power factor correction capacitors for three 60hp 480 pumps were replaced with ABB ACQ580 variable frequency drives. Ever since this upgrade, the power factor has dropped every month, dropping from 90% PF (with the...