  1. davo54

    Fluke 789

    Hi guys I have a Fluke 789 I have recently brought second hand that simulates 0-20mA instead of 4-20. Is there a fault in the meter or can you change it back to 4-20??. Have not seen it before. Also note that the source function does not work. Cheers Dave
  2. davo54

    zero error in rosemount 3051s differential flow transmitter

    Manifold/flange adaptors have been torqued properley during install?. Might need to take instrument back for a bench test
  3. davo54

    Rosemount 3051 screen not working

    Bit of a late reply sorry. I sorted the problem. the long cooper pins were misaligned on the inside end of the connection block so i couldnt see anything wrong when looking from the side. Rookie mistake..... though atleast the scrren wasnt buggered hahaha
  4. davo54

    Rosemount 3051 screen not working

    Hi After powering up a brand-new 3051(flange mounted wetleg) I noticed the screen does not show any indication(its blank). I can communicate with the instrument with Hart 375 communicator. 2 days earlier I unscrewed the screen and pulled it out to see if I could change the rotation of its...