thank you !
a bit confused about the fan motor but will run them 60Hz and see what happens
"WARNING
The motor will draw the same rated current.
The motor will run 60/50 RPM faster.
The rated torque will be the same.
CAUTION; Centrifugal Pumps and Fans will draw quite a bit more current running...
Machine has 3 devices, a pump, a fan, and a compressor
1) Pump tag say 50Hz 3X220-240D/380-415Y / 60HZ (this section is blank) Model 4J508006
2) Fan tag says Ziehl Abegg FE050-VDD.4I.6
3' 400V +/- 10% D/Y 50Hz
3) Cooling compressor tag says 460V 3-60Hz 400V 3-50Hz
Can I run this system on...