after reading so many conversations in this thread, it seems that everyone is forgotten about the existence of the SCD of the specific substation..
AFAIK, the heart of 61850 is SCD...
without SCD, you can not expand/integrate with third party IED...
CMIIW,
w33ch00
=61850newbiers=
Hi Marco1996,
AFAIK.. Areva's IED that has 61850 capability only those that has digit "4" in the middle.. such as P14x..P74x.. etc. CMIIW..
Regarding the ICD files of P139, which type are you having at the moment? is it 613 or 614 ? If 613, is it 209 or 210 ?You need to have the correct ICD...