Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations cowski on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. foley6

    intermittent high velocities during fire flows

    I need to clarify that the buildings are four stories and each floor is 18,750 sf.
  2. foley6

    intermittent high velocities during fire flows

    You're right the flow is approx. 17 ft/sec. The development is an apartment complex and we the used the 2006 IFC requirements for the fire flow. The construction type is V-A, the buildings are sprinkled and around 75,000 sf for each building.
  3. foley6

    intermittent high velocities during fire flows

    yes..the hydrant was tested and we got 1,250 gpm out of one eye. All of the joints will be restrained with megalugs and a concrete collar will be poured at the 6" to 10" transition. All of the valves on this main are gate valves that close pretty slowly. Thanks
  4. foley6

    Fire Flow Requirement according to 2006 IFC

    It did change to 75% reduction if you have approved sprinkler systems.
  5. foley6

    intermittent high velocities during fire flows

    At least 6 hydrants will be added. The required fire flow is 1500 gpm. No, the line will not be looped back to the existing main. There are no significant elevation changes. The development would be without water until the main is fixed. Thanks
  6. foley6

    intermittent high velocities during fire flows

    Yes, we're going to relocate the existing hydrant and add some more in the development.
  7. foley6

    Fire Flow Requirement according to 2006 IFC

    I downloaded the 2006 ifc and found my answer.
  8. foley6

    Fire Flow Requirement according to 2006 IFC

    Did the reduction in fire flow requirement due to sprinklers change from 50% to 75% reduction from the 2003 IFC to the 2006 IFC? Thanks
  9. foley6

    intermittent high velocities during fire flows

    Yes, we have spoken with the water owner and they approved it.
  10. foley6

    intermittent high velocities during fire flows

    I have a project that was supposed to have a 16" watermain in front of the development. It turns out that the watermain is under a major roadway and is really deep. There is a hydrant in front of the development that we are considering taking off and extending a 10" main into the development...

Part and Inventory Search