  1. PRS2000

    NEC 2020 table 310.6 or article 400 for a 3-conductor VFD cable?

    Check NFPA 79 -12.6 Conductor Sizing and you'll see where 16 or 18 AWG can be used if certain conditions are met. 16 AWG is under 12.6.1.1 and 18 AWG is under 12.6.1.2