The assembly stage of my project (A 390 MVAr Static VAr Compensator) is nearby and I need to know what may be considered as standard tools and equipment for this stage.
The equipment to be installed consists...
Well, speaking from experience, I am managing an Energy Compensation Project in Mexico City with colleagues in Germany (for Control and Protection, as well as PM and Procurement) and in Colombia (exclusively for Civil Engineering).
What I found to be the biggest problem so far is that my...
Hi everyone,
I have an issue with my regular transformer supplier. We need 4 single-phase power transformers (3+1, 400 / 16.7 kV, 60/80/100 MVA; 1F) for a Static VAr Compensator, the problem is that after the initial harmonic measurements, the harmonic content in the grid turned out to be 72A...
Hi ScottyUK,
Yeah, I'm talking about single phase circuits, I'm sorry my english is getting rustier by the day.
About triplen harmonics, thats what I was referring to, on single phase circuits the harmonic is unable to propagate to the rest of the system and as it turns out, I was thinking of...
Hi 86Ranger,
The 3rd harmonic usually cancels out on mono-phasic grids, but in three-phase grids the harmonic series is not zeroed at the common point, therefore it isn't cancelled.
Cheers!