    Auto TXFMR and Wye-Gndd/Wye-Gndd TXFMR zero sequence network

    As there is no connection from either neutal to earth / ground, no earth fault current can flow through the transformer, or be sourced from the transformer at HV or MV. This is shown in the table from the Schneider NPAG book, where the top diagram represents the condition described. All the...