Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Tek-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. kobavr

    transformer oil treatment plant

    Hi everyone, Do you recommend any brand for "transformer oil treatment plant" for site works? Thanks in advance.
  2. kobavr

    power system analyse tool

    Can we use this for professional.?
  3. kobavr

    power system analyse tool

    Hi everybody, Which tool you suggest? The best is Etap, Neplan or another one?
  4. kobavr

    DC Resistance difference between phases

    Hi everybody, I tested 180 MVA, YNd1 transformer secondary winding DC resistance as follows, a-b = 2,5 ohm b-c = 3,5 ohm c-a = 2,5 ohm What can be the reason of this test result? Why "b-c" resistance is different? Thanks in advance..
  5. kobavr

    Hobby job from a rural trout farm...they need help

    Hi everyone, I want to learn that can we generate some volts using a 3phase 380V motor.? For 1500 rpm, there is a wheel working with water flow and some reductor. Just with rotating the motor's rotor, can we read some volts on stator and can we energize some lamps. Thank you..
  6. kobavr

    "vector shift relay" or "rate of change of frequency relay"

    Marmite, Generator will remain connected servicing the site load.
  7. kobavr

    "vector shift relay" or "rate of change of frequency relay"

    ScottyUK, Once the grid shuts down, does any vector shift appear with generator voltage? Somewhere I read that ROCOF relay is better for this situation
  8. kobavr

    "vector shift relay" or "rate of change of frequency relay"

    Hi everyone, There is a cogeneration plant synchronized with the grid and there is coupling circuit breaker for connection to grid. When grid further breaker opens, we want to trip the coupling breaker. Which one of "vector shift relay" and "rate of change of frequency relay" can overcome this...
  9. kobavr

    Motor Protection 51 Settings

    Hi, How can we set motor 51 protections low set, high set or IDMT?
  10. kobavr

    generator differential

    The relay model is A20. (just generator diff) I solved the problem today. Polarities has changed, so I do the correct wiring. Now relay sees the correct values and angles. thanks all of you
  11. kobavr

    generator differential

    The transformer is Ynd11
  12. kobavr

    generator differential

    hi, we have a problem about current angles for generator differential protection-REG670 relay. Between generator and transformer there is no CB. CB is after transformer. And for synchronizing with grid, they did replace B and C phases on the primary side(grid side) of transformer. Does this...
  13. kobavr

    sep relays

    Hi everyone, I have tested some generator protection relays branded SEP at a power plant. I have a problem with U< function, it is blocked in system de-energized condition. I couldnt test U< function, I cannot find any documentation about these brand ? Do you now any about it or the website of...
  14. kobavr

    battery

    Does battery acid level affect the capacity of battery?
  15. kobavr

    ABB CAP 505 installing problem

    Hi I cannot install ABB CAP505 software on Windows 7. Problem may be related to MicroSCADA account problem. how can I overcome this problem? thanks
  16. kobavr

    article-paper references

    Primary-secondary testing, protection ,power system.
  17. kobavr

    article-paper references

    Hi, Can you give some sources on the internet to attain articles and papers?
  18. kobavr

    IED software

    How can I attain the IED connectivity packages(like ABB) or IED drivers (like Siemens) for Alstom Micom relays? I didnt find on the internet.
  19. kobavr

    zero sequence

    Thank you. Do you have a link to download St. Pierre's Short Circuit book.?
  20. kobavr

    zero sequence

    hi, How can we calculate the zero sequence impedance of a transformer? Can we do by using nameplate values?
Back