Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

Search results for query: *

  1. wcaseyharman

    Latest 'top-3' power transformer manufacturers

    Many of my company’s generator step up transformers (US utility) came from Waukesha, which is now GE Prolec. Other manufacturers that we have are Hico (out of Korea) and Delta Star.
  2. wcaseyharman

    Grounding Transformer In distributed wind generation

    PTs on the utility side would be the best and easiest to set. I’m guessing you could probably make due with gen side PTs if you had to, since the gen voltage will likely drop pretty low for a fault on the utility side, but you’d have to model it to be sure.
  3. wcaseyharman

    Riser sizing for ungrounded systems or neutral grounded systems

    Perhaps this might be useful to you: All of our large generators are high resistance grounded. Regardless, the generator enclosure and everything else in the plant is grounded to the ground grid by two 4/0 grounds minimum. This includes plants built in the last 60 years by Black and Veatch...
  4. wcaseyharman

    BESTCOMS_DECS100_11000 - Error "Communication port is not responding"

    One thing that has also bit me is making sure I’m using the right serial cable (null modem versus straight-through). My recollection is you need to use a straight-through cable, but I’ve only worked on DECS400s.
  5. wcaseyharman

    Voltage Transformer Wye Ungrounded Pri - Wye Grounded Sec Question

    General Electrical large gas and steam turbine generators almost exclusively use open delta PTs on the medium voltage system to address the issue of PT secondary faults tripping the NGR ground detection. I looked back and found open delta PTs as far back as 1935 on a GE hydro generator up to the...
  6. wcaseyharman

    PT Ferroresonance vs Modern SEL relay

    I’ve installed resistors that way exactly once. Using aux PTs and a broken delta connection seems much preferable as it doesn’t load the PT under normal operation and possibly reduce the measurement accuracy - the PTs would only be loaded under ground fault conditions. Edit - as an aside I...
  7. wcaseyharman

    Grounding Transformer In distributed wind generation

    1) do you have transfer trip installed so your recloser trips when the utility breaker opens, or are you planning on trying to detect an island with voltage or frequency? It seems like unless you have a communication scheme it would be wise to detect faults on the utility system to minimize the...
  8. wcaseyharman

    Dual Fuel Generation

    I’m assuming you need the 4 for redundancy but the Siemens SGT400 is 10MW and I think they might make that in a tri-fuel: hydrogen, natural gas and diesel.
  9. wcaseyharman

    Grounding Transformer In distributed wind generation

    I was part of this discussion in my utility for a while before I got too busy. Many if not most utilities use an effectively grounded distribution system. Effectively grounded is defined as X0 =< 3*X1. One of the main reasons to effectively ground a system is it allows you to connect line to...
  10. wcaseyharman

    Auto Transfer Switch in place of Low Voltage breaker

    We installed several for station service applications in our generating stations over the last 5 years. All of them were basically switched molded case breaker type, and several were service entrance rated.
  11. wcaseyharman

    When to island industrial plant from utility?

    Voltage and Frequency are typical interconnection relay types for islanding scenarios. If there are close in faults on the utility that your relays could see you could apply directional overcurrent or distance relaying - I am doing sensitive reverse fault settings for an intentional island at...
  12. wcaseyharman

    IEEE type AC1A Exciter model in PSS/E

    I’m pretty sure that’s the voltage droop/line drop compensation from the generator model (Xc*I_stator)
  13. wcaseyharman

    Question regarding steam turbine Generator Current transformers (multi core vs dedicated)

    If the machine is conventionally grounded with high resistance there is insufficient fault current near the neutral point to pickup the differential anyway. The main protection of your neutral transformer and resistor is your neutral overvoltage/overcurrent relay 59N or 50N (mostly have seen the...
  14. wcaseyharman

    Use of voltage regulators with step-up transformer on distributed generation

    My take: as noted in the thread above by bacon4life, what would determine the separate regulators are needed is the allowable voltage range of the gen, and what is the allowable voltage range of the line, and consider any VARS present or required that would boost or voltage the gen side voltage...
  15. wcaseyharman

    Why isn't the immediate upstream breaker tripping in my 400V Arc Flash simulation?

    In SKM powertools there’s a check box in the report options to include bus/line side arc flash in the analysis, which gives the same result as you have here. I’m not sure if that’s a thing with ETAP but you might check your arc flash analysis options and see if there’s an equivalent setting.
  16. wcaseyharman

    Load Flow Voltage Distortion Across Transformers

    If I were approaching this problem I would looks at - load current between the two cases - do vars change much. - possible saturation modeling in SKM. By lowering the HS taps the transformer would be operating farther up on the BH curve. Just some thoughts that might help.
  17. wcaseyharman

    Large Generator Exciter Air gap

    What does “internal flashover” mean? Arcing in the AVR rectifier? What equipment is arcing? And you can restart your machine? Anytime we had failed equipment in the AVR cabinet (granted, most of them are static exciters with a large bridge) something fried, like a SCR “puck” and the exciter...
  18. wcaseyharman

    Arcing fault at 480/277V panelboard, overcurrent protection, and grounding

    That’s a good point about a fire caused by load current through a high resistant connection, that certainly would explain the fuses not operating. We’ve seen failures like that which caused quite a bit of damage and ended up leading to a fault.
  19. wcaseyharman

    Arcing fault at 480/277V panelboard, overcurrent protection, and grounding

    In my experience arcing around connectors suggests high resistance connections and intermittent contact, most likely due to being loose. With a high resistance in the ground connection at the disconnect there could be insufficient fault current to blow the fuses when a ground fault occurs. Loose...
  20. wcaseyharman

    Remaining Life Assesment for Electrical Equipment

    CEATI has some good condition assessment guides for thermal and hydro electric generation and balance of plant systems. This might be useful to you, at least for those systems found within thermal and hydro generating stations. The hydro guide is called HydroAMP
Back
Top