  1. KINGSPRINKLER

    Wet sprinkler piping in attic areas

    Good memory, The illustrations you're looking for are in the 1996 handbook, NFPA 13D, figures A-4.3.1 (a thru e,) pages 637-641. I understand that they are showing CPVC in a 13D system, but thats were its at. Hope this helps. Glen
  2. KINGSPRINKLER

    Storage over 40'-0"

    Again thanks to all that responded. We are aware of head limitations, It's just that the ridge height is 41'-4", We don't want to give them K25 throughtout if we don't have to.
  3. KINGSPRINKLER

    Storage over 40'-0"

    There is no drop in the roof structure, just the roof slope 1/4" in 12", No draft stop as well. Glen
  4. KINGSPRINKLER

    Storage over 40'-0"

    We are in the process of bidding a rather large ESFR protected warehouse, ( almost 1 million sq.ft. ). Only 10% of the building has a roof height over 40'-0". Our question, Is it acceptable to use K25 heads for the systems with roof heights over 40'-0" & K17 heads for systems with roof heights...
  5. KINGSPRINKLER

    rapid line in hydracad messed up

    I agree with 3D, Autosprink is my choice & I to am eagerly waiting for VR7/8, compatible with Vista. Glen
  6. KINGSPRINKLER

    Dry system loop

    Thanks to all, I'm always adding to my knowledge of this ever expanding field. We don't do many dry systems here in northern California.
  7. KINGSPRINKLER

    Dry system loop

    Is it acceptable to loop a dry system? I know you can't grid one, but a loop?