  1. PedrohsPrado

    Help - Difference Between Two Level Transmitters (DP diaphragm seal)

    Georgeverghese, Both instruments work for total level (level of liquid hydrocarbon). They are installed in a position that is expected to have condensed hydrocarbon. So they are not designed to measure the interface between liquid HC and Glicol+water. The tubing line that you mentioned is the...
  2. PedrohsPrado

    Help - Difference Between Two Level Transmitters (DP diaphragm seal)

    Hello Danw2, I used the following data to calculate the head temperature error: See attached the error calculation from Rosemount Instrument Toolkit. Best Regards, Pedro Henrique Sousa Prado...
  3. PedrohsPrado

    Help - Difference Between Two Level Transmitters (DP diaphragm seal)

    Danw2, thank you very much for your attention. The graph unit is percentage. The difference betwen the transmitters vary from 5% to 10% (most in 8% - 80mm in level as we have 1000mm between process connections). In the graph, the yellow trend is the percentage difference betweem them. As our...
  4. PedrohsPrado

    Help - Difference Between Two Level Transmitters (DP diaphragm seal)

    Dear, I am having problems with level measurement in a vessel. In this vessel, we have 2 level transmitters (one for safety and one for control) and both are DP transmitter with diaphragm seal. Those transmitters are connected in different process connection, being them: - Control Level...