  1. zlatkodo

    Help changing direction electric phase 1 motor

    If the markings on the wires coming out of the motor are standard, the only thing you need to do is swap the wires labeled Z1 and Z2. Winding Design and Motor Repair
  2. zlatkodo

    380V/60HZ/3PH POWER SUPPLY

    It's good to know. Someone might think that you are the moderator/owner of this forum as well not just ordinary member as others.
  3. zlatkodo

    12V DC Motor in Light Fixture with Dimmer & 12V DC to 110V AC Inverter

    Read the product description before you buy that junk. BTW, this kind of post doesn't belong on electrical engineering. It's more suited for a hobby forum.
  4. zlatkodo

    380V/60HZ/3PH POWER SUPPLY

    Incidentally, how can you tell OP is logging in from the Philippines? Enlighten the rest of us.
  5. zlatkodo

    Can anyone assist with a PAM Motor

    A winding diagram for this particular PAM two-speed winding, and for any other PAM, PPM, or Dahlander two-speed winding, can be found at the link below. Link
  6. zlatkodo

    Inexplicable motor failures

    Hi, eeprom, Please attach a photo of the motor nameplate. Provide a bit more information about the maintenance history of these motors. Do the problems occur from the very beginning or only after rewinding? Very often, the only measure that a service center takes in the case of "inverter...
  7. zlatkodo

    Split Phase Motor Connection Help

    Sorry JMGotts, but your last post and the diagram look a bit confusing. Besides, you didn't draw the thermal protection that exists in the motor (usually close to zero resistance). My suggestion is to take the motor to a service center where they can properly test, label, and connect it to...
  8. zlatkodo

    Split Phase Motor Connection Help

    It's a single-speed motor. ACW
  9. zlatkodo

    230V Connected Electric Motor Running Opposite Direction When Connected for 460V

    A standard dual-voltage motor with a voltage ratio of 1:2 must have 9 or 12 leads, not 6. A 6-lead motor can also be a dual-voltage motor, but with a voltage ratio of 1:1.73 (not 1:2). Internal & External Motor Wiring
  10. zlatkodo

    Inquiry about missing post

    I'm wondering where my post from yesterday about the design of unbalanced three-phase windings went. Is it a technical issue, or was the post removed for moderation reasons? If it's a technical problem, I'll be happy to repost it. However, if it was removed, it would be helpful to understand...
  11. zlatkodo

    Motor 250KW Seimens overload and temperature rising

    At first sight, it seems that the issue might be related to the compressor rather than the motor. Has the true cause of the previous failure been identified and resolved? Another point to clarify is the statement: What exactly does that mean? Many winders consider only the turns per coil...
  12. zlatkodo

    New IE4 Motor - Pulling more Amps but less kW

    The fact that the FLA (Full Load Amps) of the new motor is higher than that of the old one does not mean that the new motor draws more current than the old one. You should only compare the actual running Amps of both motors rather than the FLA values from the nameplate. Regards Winding Design...
  13. zlatkodo

    Hall Sensor Spacing for BLDC Motor

    Hi, gb2835 The winding diagram of a 42-pole winding with 36 slots is attached (if it is a three-phase two-layer winding). It may help as it shows which coils belong to each phase. More on this topic...
  14. zlatkodo

    3-Phase Induction Motor starting problems (Locked Motor & abnormal loud sound)

    If there's only one motor involved and if this has been happening from the very beginning since it was installed, it's possible that there's a weak winding design issue, especially on the rotor. Something might have gone wrong with the custom motor design. ACW
  15. zlatkodo

    3-Phase Induction Motor starting problems (Locked Motor & abnormal loud sound)

    Hi, TT, I see two possible scenarios here: - Damage to one or more bars on the rotor, causing the motor to sometimes fail to start (depending on the position in which the rotor stopped). - It's possible that the power supply to the motor is weak at certain moments (for example, if another...
  16. zlatkodo

    230v 3hp sgl ph 3550/1725 rpm 2spd motor rewinding

    It is obvious that you cannot do it on your own. Take it to a service center that deals with such matters ACW
  17. zlatkodo

    motor rewinding from 480v to 575v

    The windings of this motors can be redesigned for 575V. Power and torque remain the same if the frequency is not changed. New windings cannot damage the pump or fan in any way. It is true that any motor can be damaged during excessive heating of the windings when removing the old winding, but...
  18. zlatkodo

    Want to rewind motor (single phase 220v 50 hz) into (single phase 220v 60 hz)

    Before redesigning the motor itself, I would test what happens if the motor is connected via an auto-transformer at 264 V. It is possible that you may need to experiment with the values of capacitors. Also, the centrifugal switch (if it exists) could still cause problems by disconnecting the...
  19. zlatkodo

    STAR Configured Fan Motor for DOAS