  1. imncntrl

    Why wont these two 20MW DY1 power transformers phase?

    Today was the day. H1 and H3 were swapped on MS and the two XFMR's phased. I guess the 6000 to -2000 volt difference between measured and calculated were due to loading and possibly impedance.
  2. imncntrl

    Why wont these two 20MW DY1 power transformers phase?

    Ok, one last question. Do the numbers above make sense at a 60 degree phase difference? When i run the numbers, i get 28000, 14400 and 14400.
  3. imncntrl

    Why wont these two 20MW DY1 power transformers phase?

    prc & davidbeach Thank you very much. Smallgreek. This stems from a reverse rotation to this sub from possibly 30 to 40 years ago. When the sub and line were rebuilt this year, they corrected the reverse rotation. This meant that when MS (the mobile sub) was brought in, they had to reverse...
  4. imncntrl

    Why wont these two 20MW DY1 power transformers phase?

    So I think what you are saying is that swapping H1 and H3 causes the 30 degree shift to go the opposite direction, therfore i wont have zero volts from any phase of T1 to any phase of MS?
  5. imncntrl

    Why wont these two 20MW DY1 power transformers phase?

    We have 2-20MW power transformers that we tried to phase so we could parallel.  I will call 1 of them T1 and the other MS.  T1 is a GE delta-wye (DY1) 115000-24940/14400.  MS is a WH delta-wye (DY1) multi-configuration set on 115000-24940/14400.  H1 and H3 are swapped on MS but i believe all...
  6. imncntrl

    Trying to Choose a Relay Test Set

    We are happy with our Omicron 256. It was about 30k when we bought ours about 5 years ago. Excellent support and free webinars also.