    External Static Pressure

    Approximately, in a commercial building, assume 0.1"/100ft. for the duct length entire. Then assume another 0.5" of the AHU PD. If the AHU has apecial filters then add the PD as per filters manufacturers. In a one floor office with supply and return ducting and diffusers I would...