I am trying to create a spec for a power meter installation. We want to be able to remotely monitor the power consumption through an existing on site controls system. The meter that has been purchased is an ITRON Sentinel power meter. The only communication output capable of working with the...
I require 1200A current capacity from the secondary of the service transformer to the main distribution panel.
Originally looking at this table 3 from the CEC C22.1-09 was used and found that 3 750kcmil per phase could be run to supply 1200A. However it was pointed out to that because the...