Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations KootK on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. alanElec

    Transformer and Generator Synchronization

    In one of my previous projects we had three transformers working in parallel.This required a synchrocheck relay to check the magnitude of Voltage, phase angle and frequency. However , is it possible to run a generator and Distribution transformer permanently(The generator is not used as a...
  2. alanElec

    Brass Glands & Aluminium Gland Plate

    Thanks both of you..I do not think there could arise a problem of rain or moisture since we are talking about a remote Petroleum Development area in the Middle East(Middle of the desert).Also this one is for a Chiller Plant for Accomodation blocks with little possibilities for contaminants,acid...
  3. alanElec

    Brass Glands & Aluminium Gland Plate

    Dear Waross, Thanks for your reply..But i missed your point completely regarding glycol paint. Hope thats a joke..! 1.Tha Switchgear Panel gland plate is aluminium.My cable is 1cx630 sq.mm,AWA 3 runs per phase. I'm planning to use Brass Cable Glands for this cable.I will be running these cables...
  4. alanElec

    Brass Glands & Aluminium Gland Plate

    Hi all, I have a simple but important question. Can we use Brass Glands for Aluminum Wire Armoured SIngle Core Cables ?? The gland plate material is Aluminium.
  5. alanElec

    4 Core Cables for Motor Feeders..

    No I don't have surplus cable..But out of ignorance we usually order four core cables for Motors as well.I wanted to confirm whether its right technically..Commercially speaking its a waste of money.
  6. alanElec

    4 Core Cables for Motor Feeders..

    The Four Core Cable as I mentioned above refers to 4 insulated similar conductors.It is usually used for 3ph Neutral Applications.An Yellow Green Earth Cable is run separate for the purpose of earthing. My only doubt is whether it I can I Leave one core(meant for neutral) unused when im feeding...
  7. alanElec

    4 Core Cables for Motor Feeders..

    Hi.. 1. Is it recommended to use 4 Core Cables for '3 phase applications without neutral'? Then the neutral will have to be left unterminated at either ends right..? Also would it lead to any induced currents in the neutral Core..?
  8. alanElec

    Form 4 Incoming Form 2 Outgoing LV Switchgear

    You might have heard of LV Panels with Forms of separation Form 2 and Form 4.Our Consultant has proposed a hybrid variant..with Form 4 Incoming section(2 incomers+1 buscoupler) and form 2 for outgoings(Hvac Loads)... Is this a common arrangement??I presume the only benefit will be cost savings..?
  9. alanElec

    Time Delay Fuses

    How to size such fuses..? Should we consider starting current also while sizing these fuses..? or is it FLC? I am confused because my consultant has asked me to confirm a 250 A upstream Switch fuse isolator for 226 A FLC downstream panel...
  10. alanElec

    Time Delay Fuses

    I would like to know weather fuses used in motor starters are time delay fuses.Please find the specific fuse type we have used in the attached Image..Are these fuses time delay fuses..?
  11. alanElec

    Chilled Water Pump Starter

    Yess..Micrologic 6.0 A...Schneider actually got the local agent to respond..He said would send a detail response tomorrow.
  12. alanElec

    Chilled Water Pump Starter

    ScottyUk, I have done my bit of searching & researching..I have checked the time current characteristic of the breaker..from that it should hold even higher currents..i also send a technical query to schneider regarding this..But the consultant has advised us to use starters of the pump hence...
  13. alanElec

    Chilled Water Pump Starter

    Thanks a lot ScottyUK..It has always been like this for me..I cant find a new job due to lack of experience...and fed up asking senior engineers for guidance..they wont help as they don't want to take responsibility..
  14. alanElec

    Chilled Water Pump Starter

    Thanks Lionel & X49.. When I have both Chillers,one pump n minor load running Total FLA is 2145..at this time if the pump starts ,the total current will be 2145+555=2700A..Im just wondering if this could be a problem for the transformer..Also can the 2500 A Breaker withstand this without...
  15. alanElec

    Complex Issue..Need Expert Help

    http://hto.power.schneider-electric.com/CBT/Apps/CurveCoordination.aspx?lang=en-GB&regulation=EuropeCenelec#Discrimination I got the curves in the above link for model: Masterpact NW25H2 Micrologic 6.0 A..Can you confirm weather this can hold 2700 A for 10/20 sec?
  16. alanElec

    Complex Issue..Need Expert Help

    I already downloaded curve direct..But Im not sure as to the conclusion from that.Y axis it has time in sec..and x-axis they have current..So I need to check the intersection of 2600 A and note how mucg time it can hold right? Can you check out n tell me?
  17. alanElec

    Complex Issue..Need Expert Help

    The transformer size is 1600 KVA.With rated amps 2100 Amps...The breaker is 2500A 4P,drawout motorized acb with micrologic trip unit with O/L,S/C & E/F protection-100 KA/1sec,make:schneider elctric,Model:NW25 H2+Micrologic 6.0 A..The locked rotor starting time of pump is 10 sec as per motor data...
  18. alanElec

    Chilled Water Pump Starter

    The transformer size is 1600 KVA.With rated amps 2100 Amps...The breaker is 2500A 4P,drawout motorized acb with micrologic trip unit with O/L,S/C & E/F protection-100 KA/1sec,make:schneider elctric,Model:NW25 H2+Micrologic 6.0 A..The locked rotor starting time of pump is 10 sec as per motor data...
  19. alanElec

    Chilled Water Pump Starter

    I have 45 KW Chilled water constant flow pump.It was earlier proposed to start it by DOL.But now due to limitation in incomer breaker size and transformer capacity we have to go for another method of starting.Which method can I use so that I can keep starting current to the least possible...
  20. alanElec

    Conversion of 3PH 480V 60Hz Supply into 3PH+N 400V 50Hz Supply using Static Frequency Converter

    It is highly recommended that you take support of the sfc manufacturer or their local agent in Abudhabi.Hope they are competent enough to solve this issue. Also consult the FCU factory of the possible effects of using 60 Hz instead of 50 Hz. You might be knowing the outcome, but better to ask...

Part and Inventory Search