Thanks to everyone for commenting. I posted the same question to General Cable, their response with attachements:
In response to your query, once the cable has been positioned, we recommend clamp supports ate nominal intervals of 6 meters.
The clamps should be sized to the diameter of the...
Manufactures advise the maximum self support length and or pulling tension details for this type of cable pulled vertically up by its phase conductors. I have not found any information on the vertical support intervals once pulled. It's become a standard in the mining industry to band the outer...
Manufactures advise the maximum self support length and or pulling tension details for this type of cable pulled vertically up by its phase conductors. I have not found any information on the vertical support intervals once pulled. It's become a standard in the mining industry to band the outer...
Thinking about a 5KV SHD-GC Cable with an integral shielded CAT6 cable built into the cable. Cable manufacture advised that they can supply this (special order). The pairs within the CAT 6 would be utilized for long distance Ethernet communications using Ruggedcom EoVDSL modems at each end. The...
Have a situation were a genset (600V detla connected) is used to provide emergency power. The system voltage is 600v, normaly supplied from a 1mva delta / wye transformer that is resistance grounded via a 69ohm NGR. The questions is, with the high side of the 1mva transformer open, would the NGR...