  1. sgelec

    PROTECTION RELAYS FOR ALTERNATOR OF 2000kVA RATING

    reverse power relay is also incorporate if synchronising with grid. rest mentioned will be sufficient. thanks
  2. sgelec

    Motor Current

    u have not mentioned the motor winding connection, feeder rating should be capable of drawing the starting current, the motor no load current will be as observed in many such practical cases is about 20-25% of FLC.
  3. sgelec

    Installation of motor at far distance

    as if the voltage drop is not above limits, please also check for short circuit at motor terminal in view of cable short circuit capacity, i have no idea about any sta--ry requirement. thanks