Bob,
You are right in saying that the winding process determines the amount of wire that can fit. As long as the winder conforms to the "layer" winding technique, you can come quite close as follows;
Turns per layer = length/OD wire.
No of layers = radial hight/OD wire.
Total turns = Turns...
A pity that I was called in at the end of the thing, so no photo's etc. Sorry for the Cu size, blonde moment! It should be 2.8 x 10.8mm.
The distribution% comes from an anaylisis of the summed strand locations. 89% says that the strand starting at that position occupies 89% of the bar's...
The machine design could have been before Roebel? Made by AEI. (Ran for 50 years). They had a straight (2 knuckle) evolute in the NCE with a two knuckle, transposed cross - over evolute in the CE. (Two clips per stack). Worst distribution was 81%, then 87%, 92%, etc.
The new...
Hi Everyone,
I have been involved in the post mortem of a 60MVA H2 cooled turbo generator failure.