Hi All,
I have a project with below criteria,
OA-45'C @90%RH
RA-23'C@50%RH
Fresh air ratio 27%
Supply air -14'C
RSHF-0.9
GSHF-0.2.
Supply air flow- 25000 CMH
When I draw a line starting from mixing air point align with GSHF it touch to the saturated line before reaching to target adp of 9'C...
Hi,
If the self elevating jack up drilling rig is following Modu code, the ventilators need to install weather tight closing appliance if the ventilators are less than 4.5 m above the main deck. We do have the shut off dampers to be able to close the compartment it serve at main deck. But I do...
Hi,
If the self elevating jack up drilling rig is following Modu code, the ventilators need to install weather tight closing appliance if the ventilators are less than 4.5 m above the main deck. We do have the shut off dampers to be able to close the compartment it serve at main deck. But I do...
Hi,
Would like to get your advice for the product latent load calculation for beef.
According to ashrae , Latent Load= Mass x ( Latent heat fusion)/ Pull down time. The question is that the when the provision is already freezed at -4"C at arrival. If so can we neglect the latent load?
Hi,
Our project is under Gibraltar Administration and would like to seek your advice for the MED certification. Is this items is required to submit MED Module B & D certificates to class? If so the certification is for weather-tightness or the asbestos free. Thanks for your advice.
I am very sure that the certificate for the water tight doors and weather tight doors are necessary to submit to class. But kindly advice about the weather tight louver. Do we need certificate?