Thanks for your concern but I probably mis spoke calling this company a High Voltage specialist. They are equipted to monitor our problems because of what they do primarily. Our company does not have the monitoring equipment. Anyways... looking back on other post.... The welding does not...
More INFO
Now we part of our p[roblem solved. When you "key" a Motorola radio near a panel with the door open every breaker trips at once. When you key it near the panel with the door closed only one or two will trip. So some of our issue is people leaving panel doors open... Now the part to...
We are thinking that the welding cables are causing our problems. We have tried bring additional grounds to the transformers but to no avail.... The runs are relatively short. 40 feet of wire between panels. In some cases the entire panel will trip with out any load on it.... Thanks for the...
I am on a project here in Las Vegas working on a temp power crew. The problems are with 1p 20A Gfi breakers. Siemans panels... We have 4 different risers feeding different areas. All areas seem to be affected. We have tried bringing a ground from another area.... checked for loose neutrals...