Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations GregLocock on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. Ekow123

    Gas turbine sychronizing breaker opens immediately its synchronizes

    Hi all, I am a visiting engineer at frame 9e power plant.The gas turbine starts and accelerates to full speed no load and whenever they about synchronizing,the breaker closes and opens after some few seconds. The mass flow rate of the distillate fuel fluctuates and never keeps increasing.It...
  2. Ekow123

    Vertical pumps tripping

    Thank you for your inputs so far.. I have been out of town for sometime now that is why I have not replied. These pumps are vertical axial flow centrifugal pumps. Presently,the problem has stopped after we performed the following; 1. cleaned the steam turbine condenser outlet to the cooling...
  3. Ekow123

    Vertical pumps tripping

    The pump is a low head high flow centrifugal pump.The design TDH is 17 m and the design flow is 7.5m3/s.These pumps take a suction from our cooling tower basin of about 8m deep.The inlet temperatures of the circulating seawater at the discharge of the pump ranges between 32 deg C TO 35 deg...
  4. Ekow123

    Vertical pumps tripping

    We run a 2*100 pump skid in our circulating water system for the cooling of our steam turbine. One of the pumps tripped on high motor current with equivalent high discharge pressure and high vibration,the other pump on auto-standby also tripped within a minute on high electric current,high...

Part and Inventory Search