Why does it have pulls to begin with???
REQUIRED BY NFPA 72 AND NFPA 101
What fire code are they under ??
NFPA 72, NFPA 101, UFC 4-211-01N Aircraft Maintenance Hangars: Type I, Type II and Type III
Do they have a code / standard section to reference requirement??
NFPA 101 SECTION 9.6.2.4...
A local AHJ on an aircraft hangar project that my firm is working on is requesting the addition of fire alarm manual pull stations at the man doors within a 240ft.long aircraft hangar door. Keep in mind the 240ft.long hangar door is operable so a hard wired connection would not be optimum. Has...