To clarify, the second column is in kWh.
The kWh for 1 consumer also doesn't increase linearly:
First column is transformer kva size, the second is kwh, and again this is for just 1 consumer:
3 300
5 500
7.5 1000
10 2500
15 4000
25 7500
37.5 12500
50 16000
Does this guide...
Here at an electric distribution coop, we have always used a guide probably from the old REA days for sizing transformers. I’m wondering, though, why does load capacity go down with more customers?
Example: for a 25 kva transformer, the first column is number of customers and the second is the...