  1. aruskuat

    Ambinet Air Temperature for Conductor Derating

    You need to use correction factor of temperature based on maximum operating temperature, typically standard ambient temp is 40C for above ground and 20 C for under ground installation. You can find it in IEEE 399
  2. aruskuat

    3.3kV Generator Grounding

    If you have the same generator size, it is allowed to make a Common Grounding Point because it is easy to applying selective relaying. Actually you can refer to IEEE 142 and ANSI C37.102
  3. aruskuat

    Converting three phase power transmission to single phase power

    actually you can use scott-T connection in order to make the balanced when you use 1 phase from 3 phase
  4. aruskuat

    Generator Neutral Grounding Method

    Agree with that, high resistance grounding mostly used in generators <25A
  5. aruskuat

    TRANSFORMER INRUSH CURRENT

    There is specific value for 3 winding TR, here is : 0 – 1000 kVA : 9.5 – 12 x In 1000 – 10000 kVA : 5.9 – 11.4 x In 10000-100000 kVA : 3.6 – 7.5 x In > 100000 kVA : 2.5 – 4.8 x In but there is no specific value for tow winding TR, it can reach for 40 x, you can refer to IEC 60076. The...
  6. aruskuat

    Generator Neutral Grounding Method

    Kibz, here is my answer : 1. Is 10.5 kV line-line or line-ground voltage? The rated voltage of NGR is line-ground voltage of your generator 2. The purpose of using high-resistance grounding, according to IEEE 142 and ANSI C37.101 is to limit the level of over voltage and SC when there is fault...
  7. aruskuat

    tying DC voltage to a current circuit

    it will make the ct saturated then the relationship between primary and secondary will be highly unlinear