Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations GregLocock on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. frizzmizz

    Burying a 12" gate valve underground

    Thanks, I will post an updated on what path we go with.
  2. frizzmizz

    Burying a 12" gate valve underground

    Thanks for the suggestions everyone. I did consider valve pit but this is a very low risk water service and client would like to avoid getting a valve pit to reduce project costs as much as possible. LittleInch, do you know of any vendors that provide valves with extended stem as shown in the...
  3. frizzmizz

    Burying a 12" gate valve underground

    Hello everyone, I am working on an underground Recycled Cooling Water Line and we are adding a 12" drain to this line which requires the addition of an underground 12" gate valve. Design conditions are 24C and 100psi. I am just wondering what the best way to go about this would be. I am...
  4. frizzmizz

    Branch connections that are not in center of header pipe? Allowed per B31.3?

    Thanks, that would make sense. Have you ever done any of the steps listed in para 304.7.2 for doing this?
  5. frizzmizz

    Branch connections that are not in center of header pipe? Allowed per B31.3?

    Hello everyone, just wondering if anyone has come across a situation where they needed to install a branch pipe on a header in a way that the center lines of the branch pipe does not intersect with the center line of header? I have attached a drawing which shows this case...
  6. frizzmizz

    Connecting AWWA Class D flange to ASME 150# flange?

    Hi rconner thanks for your input. Since we don't normally deal with AWWA C207 we don't have a copy of that standard. But it is good to know that those flanges are designed to withstand a hydro of up to 262.5 psig. Design pressure of our lines is 150 psig. Strainer max operating pressure is 175...
  7. frizzmizz

    Connecting AWWA Class D flange to ASME 150# flange?

    I looked online and found some details on the 4" AWWA Class D flange: Nominal Pipe Size - 4" Outside Diameter (A) - 9 Thickness (T) - .625 Inside Diameter (B) - 4.57 Approximate Weight (lbs) - 8 Number of Bolt Holes - 8 Diameter of Bolt Holes - 0.75 Diameter of Bolt Circle (C) -...
  8. frizzmizz

    Connecting AWWA Class D flange to ASME 150# flange?

    Hello folks, I was wondering if someone can help me with this issue. I work for an oil and gas EPC and we are currently designing a fire water system to protect one of the hydrocarbon tanks on site. All the piping is as per ASME B31.3 which is what the client pipe classes are based off...