  1. mostafashdeed

    Atrium fire sprinklers

    dear all i have aquestion below paragraphs NFPA 13 (2010 edition) 8.15.4.4 Large Openings. Closely spaced sprinklers and draft stops are not required around large openings such as those found in shopping malls, atrium buildings, and similar structures where all adjoining levels and spaces are...
  2. mostafashdeed

    fire hose reel connection

    thank you all very match
  3. mostafashdeed

    fire hose reel connection

    dear all i would like to ask about if it acceptable or not to connect fire hose reel 1.5" from sprinklers network directly after z.c.v i have searched NFPA 14 and didn’t find what allow or prevent and thanks a lot in advance
  4. mostafashdeed

    Fire hose reel connection

    dear all i would like to ask about if it acceptable or not to connect fire hose reel 1.5" from sprinklers network directly after z.c.v i have searched NFPA 14 and didn’t find what allow or prevent and thanks a lot in advance .
  5. mostafashdeed

    hello every one i have a question a

    thank you very much
  6. mostafashdeed

    hello every one i have a question a

    hello every one i have a question about fire hydrant as you know NFPA doesnt explain how to determine flow rate or pressure or distance separating hydrants so if any one has a guideline in this topic or information i will be thankful and thanks in advance .
  7. mostafashdeed

    hello every one i have a question h

    hello every one i have a question how can i determine number of risers for a building is it equal to number of zones per floor or what ?
  8. mostafashdeed

    hi every one i have a question in f

    hi every one i have a question in fire water tanks shall i put a strainer before the tank or after and why thanks in advance
  9. mostafashdeed

    if i have a tank of fuel and i want

    chicopee yes water is used for cooling to make sure tank does not affect other tasnks
  10. mostafashdeed

    if i have a tank of fuel and i want

    trashcanman' yes i use water for cooling the the tank i cant find a source for 0.1 gpm/ft2 i know that min density is 0.15 according to nfpa but at work they use 0.1 so i wanted to make sure
  11. mostafashdeed

    if i have a tank of fuel and i want

    stookeyfpe yes but where can i find such tables ?
  12. mostafashdeed

    if i have a tank of fuel and i want

    if i have a tank of fuel and i want to design cooling system for it i get water flow rate from equation Q= Area*Factor Factor is 0.1 gpm/ft.sqr and Area is Area total = shell area + roof area ? is that right ?