  1. Menford

    Dayton 230 volt single phase wiring

    Thanks SteveKW. Yes that makes sense to me. On a cap start run motor, are the run caps utilized by both the start windings and run windings? Thanks again. Glen
  2. Menford

    Dayton 230 volt single phase wiring

    The resistance from t7 to t6 is 1 ohm. From t6 to t8 is 2.3 ohm. From t7 to t8 is 2.3 ohm.
  3. Menford

    Dayton 230 volt single phase wiring

    On this Dayton motor T6, T7, and T8 have continuity. T7 is connected to centrifugal switch and the other non-labeled wire from the centrifugal switch is connected to the start caps. T4 and T5 are tied together to L1. T8 and T1 are tied together to L2. The run caps are tied in series with the...