Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations IDS on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. Darren6060

    Sizing For A Boiler Blowdown Tank?

    For blowdown tank sizing - I use Canadian Code CSA B51-09 Boiler Pressure vessel and pressure piping code. Table 1 defines the design pressure for blowoff vessel Max boiler pressure 15-300 psi use 30% of max boiler pressure but shall be at least 15 psi Over 300 psi max boiler pressure use...
  2. Darren6060

    Location of feedwater stop and check valve ASME Sec 1

    I am installing a new boiler. 35,000 pph x 150 psig saturated steam d-type. The boiler has an economizer that is isolable ie we can bypass it with 3 valves and it has its own safety valve. I usually see feedwater stop and check valves upstream of economizer. However when I got the P&ID in from...