Hi
May be this would be helpful
Your Supply is probably 240 Phase to Phase (basically 2 wires) tapped from a 3 phase source. (I have seen at some locations where 240 V Phase to Phase is generated for specific use to avoid neutral. I presume it may be the same)
You may have to provide...
Hi RajT
Yes you are correct what we have here at present is unity power factor load but we need to test as stated above. I could have done the test if I had reactive power load. But due to some constrains I can only use unity power factor. Do you have any other method of achieving the same...
Hi
The following generator is available at a particular site
Generator rating 300KW (375 KVA) , L-L Voltage 380V, L-N Voltage 220 V, Power factor 0.8, Current at 0.8 pf is 570A, Frequency 60Hz, 3phase 4 Wire System
The generator is provided with the following calibrated instruments with...