Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations IDS on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. rmarsenault

    Another maximum pressure limitation question

    Hey thanks for the advice. I went through the specs of the equipment downstream from the fire pump and determined that the fittings are rated for 750psi and the sprinklers (victaulic v2708) are rated for 250psi. As NFPA states...where portions of the system have components rated for less than...
  2. rmarsenault

    Another maximum pressure limitation question

    Hi folks. I'm new here (posting that is). I have browsed this forum several times over the last few years. You guys are knowledgeable and it is nice to see such dedicated individuals in our field. That being said, I am an engineer in Canada and my company is involved in fire protection...

Part and Inventory Search