  1. Lostinquebec

    2300v motor efficiency continued

    I’m going further on it now, if I use the “dual control” mode, it will totally unload until it’s needed, dropping the Amos to 67A. My problem now, is that the interstage temp goes too high! Lostinquebec
  2. Lostinquebec

    2300v motor efficiency continued

    There is a minimum Amperage adjustment for the motor, it basically controls the IGV. Lostinquebec
  3. Lostinquebec

    2300v motor efficiency continued

    Hey Waross, thank u so much for the break Down, what’s the 1.73 part of the equation? Lostinquebec
  4. Lostinquebec

    2300v motor efficiency continued

    I reduced the minimum allowable amperage on the machine. Lostinquebec
  5. Lostinquebec

    2300v motor efficiency continued

    So, my last thread got closed, but basically I did finally change the settings on the compressor. I successfully reduced the amps by 20 at 2300v. We are no longer blowing air out the wall. Now, my boss says that we only pay 4cents per kwhr and that we only saved about $5000 a year! Does this...
  6. Lostinquebec

    2300v motor efficiency

    And now its just a poor me rant, I'm sorry guys, i was hoping to do some good Lostinquebec
  7. Lostinquebec

    2300v motor efficiency

    Feeling pretty beat down at this point, it's like I'm surrounded by people that don't know what they should and don't want to, and ur an idiot if u try to think They actually posted a notice directed at me to not touch the machinery. My response was that we need to get the contractor to come in...
  8. Lostinquebec

    2300v motor efficiency

    Omg, and now they want to rebuild the other one because the "vibrations" are high! They're at 0.67 mils, alarm is 0.90 and trip is 1.20! I tried explaning that they were relative and change everytime the machine has had work on it. Now this one will be nice and tight too so we can scream even...
  9. Lostinquebec

    2300v motor efficiency

    Unfortunately, my workplace disagrees with me, even after I present the data that I have collected. They want that machine blowing the air out the wall (like 600cfm) Thanks for all the help Lostinquebec
  10. Lostinquebec

    2300v motor efficiency

    Thanks for all the help guys,I believe as long as I dont lower the min amps to the surge point, i'm doing a good thing by getting that blowoff closed I was just hoping to put a dollar estimate on it. Lostinquebec
  11. Lostinquebec

    2300v motor efficiency

    I believe there is actually a feature on this unit that will unload itself and idle for short periods if not needed. But we're a long ways from that Lostinquebec
  12. Lostinquebec

    2300v motor efficiency

    It's a centrifugal (turbine) type. Full capacity is rarely needed as we have less demand than before. I actually was looking for financial savings to try to prove my case. Lostinquebec
  13. Lostinquebec

    2300v motor efficiency

    I don't think so, I feel like its just been ranlike this so everybody panicks if you touch it. I have done many tests with the reduced power setting and had no adverse effects.I was just wondering about the savings. The contractor is out to lunch Lostinquebec
  14. Lostinquebec

    2300v motor efficiency

    More nfo Lostinquebechttps://files.engineering.com/getfile.aspx?folder=c4d064dc-7c0e-49d9-afdb-cdb1eaaef825&file=15419040959897096623043727382200.jpg
  15. Lostinquebec

    2300v motor efficiency

    Model 220 DA3 Lostinquebechttps://files.engineering.com/getfile.aspx?folder=91750ffc-7500-42f5-83de-392dea7ab130&file=15419037932856554764998062856254.jpg
  16. Lostinquebec

    2300v motor efficiency

    It's an elliott 3 stage centrifugal P/P Plus. Honestly I feel like either I'm missing something here, or someone doesn't understand their machine Lostinquebechttps://files.engineering.com/getfile.aspx?folder=e70d089b-8008-48b0-b2b8-f8679e709109&file=15419031755396631956759140976078.jpg
  17. Lostinquebec

    2300v motor efficiency

    Even the compressor contractor made a big deal and put out a note that this machine must blow off at all times? Lostinquebec
  18. Lostinquebec

    2300v motor efficiency

    It actually all started by trying to get the blowoff valve closed.Then they rebuilt one so ots tight now and blows off even more! Lostinquebec
  19. Lostinquebec

    2300v motor efficiency

    They also are concerned about the vibrations, which do not change really and are well within parameters, like the highest being 0.80 mils Lostinquebec
  20. Lostinquebec

    2300v motor efficiency

    Induction Motor 600hp,3565 rpm,118 psi,0.993 - 0.998 power factor My coworkers seem to be under the belief that it needs to blowoff at all times. Which at times can be half of the air produced, so say 500cfm out the wall. Lostinquebec