Hello Everyone,
I have a questions regarding the size of my discharge piping for my fire sprinkler system. The question relates to section 4.18.6.2.1 of the NFPA 20 which states " If the pipe ( Discharge piping) employs more than one elbow, the next larger pipe shall be used."
My system will...
One more question if you don't mind LCREP. If I were to pipe my testing line ( with flow meter connected ) back to my supply tanks, I could eliminate the hose valves + header?
Thanks LCREP. I will have to check through NFPA 13 to verify if a fire department connection is required. The fire sprinkler system is for a construction camp, so I believe there would be fire department connection located around the building.
Hello Everyone,
This is my first post on the forum. I'm hoping you guys can help me out with a few questions about fire sprinkler systems, particularly, regarding NFPA 20 code. I'm currently developing a Diesel driven, split horizontal pump @ 1000 gpm.
1. Hose Valves and Fire Department...